Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 4, 2019, 08:08 PM
  • 02 0694_02 0692_342019_121332.mp4

Date
03/04/2019
W/O
0756474
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00311
PipeID
P04577
Time
12:08 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7931
Sewer Name
02 WOODRUFF AVENUE TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
33
Purpose
Routine Assessment
Project
20190228DF_WOODRUFF_AVENUE_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
02 0694
Downstream MH
02 0692
Dir. of Survey
Downstream
Length Surveyed
747.9 ft.
Total Length
747.9 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 0694 to 02 0692
MH: 02 0694MH: 02 0692downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:10 PM2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG62.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"74.2 ft. MGP - General Photograph106.8 ft. MGP - General Photograph224.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4" - DEFECTIVE352.7 ft. MGP - General Photograph411.5 ft. MGP - General Photograph539.9 ft. MGP - General Photograph615.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4"746 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish746 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG746 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish746 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish747.9 ft. AMH - Downstream Manhole, Survey Ends - 1:16 PM747.9 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)747.9 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach

Observation photos (10)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG

  • General Photograph

    74.2 ft. - General Photograph

  • General Photograph

    106.8 ft. - General Photograph

  • Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4" - DEFECTIVE

    224.1 ft. - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4" - DEFECTIVE

  • General Photograph

    352.7 ft. - General Photograph

  • General Photograph

    411.5 ft. - General Photograph

  • General Photograph

    539.9 ft. - General Photograph

Observations (22)

DistanceCodeObservation
0MWM
352.7MGP
0MWL
2SAV
747.9AMH1:16 PM
2SRV
62.7TFC
2SSS
615.2TFA
411.5MGP
106.8MGP
74.2MGP
746SSS
539.9MGP
746SZ70% MAG
0AMH12:10 PM
747.9MGOGREASE THROUGHOUT THE REACH (5%)
746SRV
224.1TFCDEFECTIVE
747.9MGOPeeling & Flaking Throughout The Reach
746SAV
2SZ70% MAG

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-03-04T12:08:03-08:00
documentation
FRANKLIN, RAMIREZ, RUVALCABA
is_lateral_inspection
false