Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 21, 2019, 11:44 AM
  • 02 2089_02 1898_3212019_045525.mp4

Date
03/21/2019
W/O
0759728
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00247
PipeID
P04405
Time
4:44 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Heavy Cleaning
Media Label
H1157
Sewer Name
02 DOUGLAS AVENUE RELIEF TRUNK
City
LOS ANGLES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20190321MDM_DOUGLAS_AVENUE_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
02 2089
Downstream MH
02 1898
Dir. of Survey
Downstream
Length Surveyed
244.9 ft.
Total Length
244.9 ft.
Structural Index
3
Structural Quick
5125
Structural Rating
15
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
15
Pipe schematic from manhole 02 2089 to 02 1898
MH: 02 2089MH: 02 1898downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 3 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:55AM0 ft. MWM - Water Mark, 20 %of cross sectional area3.1 ft. FC - Fracture Circumferential, from 12 to 06 o'clock, within 8 inches of joint: YES - SLIGHT14.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - Capped17 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open41.6 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE51 ft. JOL - Joint Offset Large62.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open71.9 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SLIGHT106.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open144.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open144.2 ft. MGO - General Observation - 8" VCP194.4 ft. BVV - Broken Void Visible, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT207.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6" - Active242.9 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SLIGHT244.9 ft. AMH - Downstream Manhole, Survey Ends - 5:25AM

Observation photos (3)

  • Joint Offset Large

    51 ft. - Joint Offset Large

  • General Observation - 8" VCP

    144.2 ft. - General Observation - 8" VCP

  • Broken Void Visible, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

    194.4 ft. - Broken Void Visible, from 02 to 04 o'clock, within 8 inches of joint: YES - SLIGHT

Observations (18)

DistanceCodeObservation
3.1FCSLIGHT
242.9FCSLIGHT
17TFOpen
41.6FCHAIRLINE
207.9TFActive
194.4BVVSLIGHT
51JOL
144.2TFOpen
0MGOConn. @ Mh, 3 O' Clock. Active
71.9FCSLIGHT
0MWL
106.1TFOpen
0AMH4:55AM
244.9AMH5:25AM
0MWM
144.2MGO8" VCP
62.6TFOpen
14.4TFCCapped

Properties (6)

custom_field_three
BROKEN PIPE VOID SLIGHT FRACTURE-LARGE OFFSET
custom_field_two
2
customer
LACSD
datetime
2019-03-21T04:44:55-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false