Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2019, 08:26 AM
  • C 0099_C 0098_3192019_020836.mp4

Date
03/19/2019
W/O
0613350
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09566
Time
1:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1154
Sewer Name
C JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20190319MDM_JOINT_OUTFALL_C_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
C 0099
Downstream MH
C 0098
Dir. of Survey
Downstream
Length Surveyed
830.6 ft.
Total Length
830.6 ft.
Structural Index
4
Structural Quick
4722
Structural Rating
32
O&M Index
3
O&M Quick
4121
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
38
Pipe schematic from manhole C 0099 to C 0098
MH: C 0099MH: C 0098downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:15AM1 ft. MGO - General Observation - SMALL OPENING BOTTOM OF MH2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT2 ft. MGO - General Observation - RAISED AREA AT 12:002 ft. MGO - General Observation - 100% MAG COAT START8 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG42.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT52 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE248.9 ft. SAM - Surface Aggregate Missing, from 12 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG308.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG363.6 ft. SAM - Surface Aggregate Missing, from 12 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT486.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start525.9 ft. SAM - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT598.3 ft. SAM - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERER AGG830.2 ft. MGO - General Observation - 100% MAG COAT FINISH830.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDER MAG COAT830.2 ft. SAM - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG830.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE830.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish830.6 ft. AMH - Downstream Manhole, Survey Ends - 3:15AM

Observation photos (13)

  • General Observation - SMALL OPENING BOTTOM OF MH

    1 ft. - General Observation - SMALL OPENING BOTTOM OF MH

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - RAISED AREA AT 12:00

    2 ft. - General Observation - RAISED AREA AT 12:00

  • General Observation - 100% MAG COAT START

    2 ft. - General Observation - 100% MAG COAT START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    8 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

    42.2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    52 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Missing, from 12 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    248.9 ft. - Surface Aggregate Missing, from 12 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    308.2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 12 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

    363.6 ft. - Surface Aggregate Missing, from 12 to 04 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    486.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

    525.9 ft. - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG UNDER MAG COAT

  • Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERER AGG

    598.3 ft. - Surface Aggregate Missing, from 01 to 03 o'clock, within 8 inches of joint: NO, Start - SEVERER AGG

Observations (22)

DistanceCodeObservation
0MWL
1MGOSMALL OPENING BOTTOM OF MH
830.2MGO100% MAG COAT FINISH
0MWM
830.2SAMSEVERE AGG UNDER MAG COAT
0AMH2:15AM
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
2MGORAISED AREA AT 12:00
525.9SAMSEVERE AGG UNDER MAG COAT
308.2SAMSEVERE AGG
42.2SAMSEVERE AGG UNDER MAG COAT
52SSSPEELING CONCRETE
8SAMSEVERE AGG
830.2SAMSEVERE AGG
248.9SAMSEVERE AGG
363.6SAMSEVERE AGG UNDER MAG COAT
830.6AMH3:15AM
830.2SSSBLISTERING PEELING CONCRETE
2MGO100% MAG COAT START
830.2DAGS
486.1DAGS
598.3SAMSEVERER AGG

Properties (6)

custom_field_three
SEVERE AGG MISSING- 100% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2019-03-19T01:26:41-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTLLO
is_lateral_inspection
false