Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2019, 08:12 AM
  • C 0100_C 0099_3192019_014634.mp4

Date
03/19/2019
W/O
0613350
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00122
PipeID
P09567
Time
1:12 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1154
Sewer Name
C JOINT OUTFALL C - UNIT 3C
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Capital Improvement Program Assesment
Project
20190319MDM_JOINT_OUTFALL_C_UNIT_3C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Upstream MH
C 0100
Downstream MH
C 0099
Dir. of Survey
Downstream
Length Surveyed
922.6 ft.
Total Length
922.6 ft.
Structural Index
3
Structural Quick
4325
Structural Rating
22
O&M Index
3
O&M Quick
5122
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
31
Pipe schematic from manhole C 0100 to C 0099
MH: C 0100MH: C 0099downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM0 ft. MWL - Water Level, 60 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 100% START2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT70.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start155.6 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE408.2 ft. MGO - General Observation - 100% MAG COAT408.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT497.6 ft. TBC - Tap Break-In Capped, at 12 o'clock, -, within 8 inches of joint: NO, 8" - Capped501.5 ft. MGO - General Observation - RAISED AREA 12:00 UNDER MAG COAT START534 ft. SSS - Surface Spalling, at 12 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE ON RAISED AREA 1`2:00547.3 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG566.2 ft. SSS - Surface Spalling, from 12 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT688.7 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG725.3 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG774.3 ft. SAM - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO, Finish - SEVERE AGG922.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish922.2 ft. SAM - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG922.2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE922.2 ft. MGO - General Observation - MAG COAT 100%922.6 ft. AMH - Downstream Manhole, Survey Ends - 2:55AM

Observation photos (12)

  • General Observation - MAG COAT 100% START

    2 ft. - General Observation - MAG COAT 100% START

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    70.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

    155.6 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

  • General Observation - 100% MAG COAT

    408.2 ft. - General Observation - 100% MAG COAT

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

    408.2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: NO - BLISTERING PEELING CONCRETE UNDER MAG COAT

  • General Observation - RAISED AREA 12:00 UNDER MAG COAT START

    501.5 ft. - General Observation - RAISED AREA 12:00 UNDER MAG COAT START

  • Surface Spalling, at 12 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE ON RAISED AREA  1`2:00

    534 ft. - Surface Spalling, at 12 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE ON RAISED AREA 1`2:00

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    547.3 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 12 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

    566.2 ft. - Surface Spalling, from 12 to 02 o'clock, within 8 inches of joint: NO - PEELING CONCRETE UNDER MAG COAT

  • Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    688.7 ft. - Surface Aggregate Missing, from 12 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

    725.3 ft. - Surface Aggregate Missing, from 10 to 12 o'clock, within 8 inches of joint: NO, Start - SEVERE AGG

Observations (22)

DistanceCodeObservation
497.6TBCCapped
774.3SAMSEVERE AGG
2MGOMAG COAT 100% START
408.2MGO100% MAG COAT
566.2SSSPEELING CONCRETE UNDER MAG COAT
922.2DAGS
547.3SAMSEVERE AGG
501.5MGORAISED AREA 12:00 UNDER MAG COAT START
2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
922.2SAMSEVERE AGG
70.2DAGS
408.2SSSBLISTERING PEELING CONCRETE UNDER MAG COAT
155.6SSSBLISTERING CONCRETE
534SSSBLISTERING CONCRETE ON RAISED AREA 1`2:00
0MWM
0AMH1:50AM
922.2SSSBLISTERING PEELING CONCRETE
922.2MGOMAG COAT 100%
688.7SAMSEVERE AGG
725.3SAMSEVERE AGG
922.6AMH2:55AM
0MWL

Properties (6)

custom_field_three
SEVERE AGG MISSING -100% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2019-03-19T01:12:42-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTLLO
is_lateral_inspection
false