Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 13, 2019, 05:55 PM
  • 02 1098_02 1097_3132019_110452.mp4

Date
03/13/2019
W/O
PENDING
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00300
PipeID
P03671
Time
10:55 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1148
Sewer Name
02 RANDOLPH STREET TRUNK
City
COMMERCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Maintenance Related
Project
20190313SHO_RANDOLPH_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1098
Downstream MH
02 1097
Dir. of Survey
Downstream
Length Surveyed
347.2 ft.
Total Length
347.2 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 1098 to 02 1097
MH: 02 1098MH: 02 1097downstream0 ft. AMH - Upstream Manhole, Survey Begins - MH 10980 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area21.4 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start347.2 ft. AMH - Downstream Manhole, Survey Ends - MH 1097347.2 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    21.4 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0AMHMH 1098
0MWM
0MWL
347.2AMHMH 1097
21.4CH2
347.2CH2

Properties (5)

additional_info
LOOKING FOR ANY DAMAGE FROM POWER POLE INSTALLATION
customer
LACSD
datetime
2019-03-13T10:55:39-07:00
documentation
OBREGON, YOUNG, BRAR
is_lateral_inspection
false