Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 13, 2019, 04:17 PM
  • 02 1098A_02 1098_3132019_092940.mp4

Date
03/13/2019
W/O
PENDING
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00300
PipeID
P03672
Time
9:17 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1148
Sewer Name
02 RANDOLPH STREET TRUNK
City
COMMERCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Maintenance Related
Project
20190313SHO_RANDOLPH_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
02 1098
Downstream MH
02 1098A
Dir. of Survey
Upstream
Length Surveyed
235.8 ft.
Total Length
235.8 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 1098 to 02 1098A
MH: 02 1098MH: 02 1098Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - MH 1098A4.7 ft. CH2 - Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish216.8 ft. CH2 - Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES, Start222.1 ft. OBZ - Obstacles Other, 10 %of cross sectional area, from 04 to 06 o'clock - DEBRIS235.8 ft. MWM - Water Mark, 30 %of cross sectional area235.8 ft. AMH - Downstream Manhole, Survey Begins - MH 1098235.8 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (1)

  • Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    19 ft. - Crack Longitudinal Hinge, 2, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0MWM
19CH2
231.1CH2
235.8AMHMH 1098A
0AMHMH 1098
0MWL
13.7OBZDEBRIS

Properties (6)

additional_info
LOOKING FOR ANY DAMAGE FROM POWER POLE INSTALLATION
custom_field_two
5
customer
LACSD
datetime
2019-03-13T09:17:53-07:00
documentation
OBREGON, YOUNG, BRAR
is_lateral_inspection
false