Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2019, 10:14 AM
  • 05 1010_05 1009_3152019_040709.mp4

Date
03/15/2019
W/O
0760333
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00421
PipeID
P06243
Time
3:14 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1152
Sewer Name
05 AVIATION BOULEVARD TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
20190312MDM_AVIATION_BOULEVARD_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1010
Downstream MH
05 1009
Dir. of Survey
Downstream
Length Surveyed
349.8 ft.
Total Length
349.8 ft.
Structural Index
4
Structural Quick
5433
Structural Rating
35
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
35
Pipe schematic from manhole 05 1010 to 05 1009
MH: 05 1010MH: 05 1009downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 4:05AM2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. MGO - General Observation - MAG COAT 90% START13.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE81.5 ft. SAV - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC130.8 ft. SSS - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE157.2 ft. SAV - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC233.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR240.7 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR254.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR260.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR333.3 ft. SAV - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG343.6 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR349.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE349.4 ft. MGO - General Observation - MAG COAT 90% FINISH349.8 ft. AMH - Downstream Manhole, Survey Ends - 4:40AM

Observation photos (11)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • General Observation - MAG COAT 90% START

    2 ft. - General Observation - MAG COAT 90% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    13.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    81.5 ft. - Surface Aggregate Visible, from 08 to 10 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

    130.8 ft. - Surface Spalling, from 12 to 04 o'clock, within 8 inches of joint: NO - PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

    157.2 ft. - Surface Aggregate Visible, from 08 to 11 o'clock, within 8 inches of joint: NO - SEVERE AGG SPORATIC

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    233.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    240.7 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    254.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG

    333.3 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    343.6 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (19)

DistanceCodeObservation
349.4SSSBLISTERING PEELING CONCRETE
157.2SAVSEVERE AGG SPORATIC
0MWM
13.2SSSPEELING CONCRETE
81.5SAVSEVERE AGG SPORATIC
0MWL
260.5SRVCIRCUM REBAR
0MGOConn. @ Mh, 3 O' Clock. Active
343.6SRVCIRCUM REBAR
349.8AMH4:40AM
0AMH4:05AM
130.8SSSPEELING CONCRETE
2SSSBLISTERING PEELING CONCRETE
333.3SAVSEVERE AGG
349.4MGOMAG COAT 90% FINISH
240.7SRVCIRCUM REBAR
2MGOMAG COAT 90% START
233.7SRVCIRCUM REBAR
254.4SRVCIRCUM REBAR

Properties (6)

custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2019-03-15T03:14:40-07:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false