Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2019, 09:13 AM
  • 03 0432_03 0431_382019_021246.mp4

Date
03/08/2019
W/O
0759775
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00406
PipeID
P04980
Time
1:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1140
Sewer Name
03 WATER STREET TRUNK
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20190308MDM_WATER_STREET_TRUNK
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
03 0432
Downstream MH
03 0431
Dir. of Survey
Downstream
Length Surveyed
159.6 ft.
Total Length
159.6 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 03 0432 to 03 0431
MH: 03 0432MH: 03 0431downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:15AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE6.6 ft. IW - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES14.1 ft. IW - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES22.2 ft. IW - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AT JOINTS64.4 ft. SAP - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG67.7 ft. SRV - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR113.6 ft. SRV - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR159.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE159.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG159.1 ft. IW - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - AT JOINTS159.6 ft. AMH - Downstream Manhole, Survey Ends - 2:35AM

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AT JOINTS

    22.2 ft. - Infiltration Weeper, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - AT JOINTS

  • Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

    64.4 ft. - Surface Aggregate Projecting, from 08 to 12 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    67.7 ft. - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    113.6 ft. - Surface Reinforcement Visible, from 08 to 09 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (16)

DistanceCodeObservation
159.1SSSBLISTERING PEELING CONCRETE
0AMH2:15AM
0MGOConn. @ Mh, 3 O' Clock. Active
0MWM
2SAPSEVERE AGG
159.1SAPSEVERE AGG
159.1IWAT JOINTS
6.6IW
159.6AMH2:35AM
22.2IWAT JOINTS
2SSSBLISTERING PEELING CONCRETE
67.7SRVCIRCUM REBAR
113.6SRVCIRCUM REBAR
64.4SAPSEVERE AGG
0MWL
14.1IW

Properties (6)

custom_field_three
CIRCUM REBAR VISIBLE
custom_field_two
2
customer
LACSD
datetime
2019-03-08T01:13:49-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false