Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2019, 07:49 PM
  • C 0121_C 0120_382019_120236.mp4

Date
03/08/2019
W/O
0759956
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00127
PipeID
P09644
Time
11:49 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7937
Sewer Name
C JOINT OUTFALL C - UNIT 4B
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
20
Purpose
Capital Improvement Program Assesment
Project
20190308DF_JOINT_OUTFALL_C_UNIT_4B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Upstream MH
C 0121
Downstream MH
C 0120
Dir. of Survey
Downstream
Length Surveyed
780.6 ft.
Total Length
780.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole C 0121 to C 0120
MH: C 0121MH: C 0120downstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:52 AM0.1 ft. MWM - Water Mark, 35 %of cross sectional area0.1 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 100% MAG102.9 ft. MGP - General Photograph500.5 ft. MGP - General Photograph505 ft. MGP - General Photograph613 ft. MGP - General Photograph700 ft. MGP - General Photograph775.1 ft. DAR - Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish775.2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 100% MAG780.6 ft. AMH - Downstream Manhole, Survey Ends - 12:27 PM780.6 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (7)

  • Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Ragging, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 100% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 100% MAG

  • General Photograph

    102.9 ft. - General Photograph

  • General Photograph

    500.5 ft. - General Photograph

  • General Photograph

    505 ft. - General Photograph

  • General Photograph

    613 ft. - General Photograph

  • General Photograph

    700 ft. - General Photograph

Observations (14)

DistanceCodeObservation
0.1MWM
102.9MGP
0AMH11:52 AM
613MGP
780.6AMH12:27 PM
2DAR
2SZ100% MAG
775.2SZ100% MAG
505MGP
500.5MGP
775.1DAR
700MGP
780.6MGOGREASE THROUGHOUT THE REACH (5%)
0.1MWL

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2019-03-08T11:49:00-08:00
documentation
FRANKLIN, IGNACIO, RAMIREZ, RUVALCABA
is_lateral_inspection
false