Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2019, 07:59 AM
  • 08 0010_08 0009_412019_041739.mp4

Date
04/01/2019
W/O
0763628
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00010
Time
12:59 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1166
Sewer Name
08 MAIN STREET TRUNK
City
CARSON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Capital Improvement Program Assesment
Project
20190401MDM_MAIN_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
33 in.
Upstream MH
08 0010
Downstream MH
08 0009
Dir. of Survey
Downstream
Length Surveyed
337.8 ft.
Total Length
337.8 ft.
Structural Index
5
Structural Quick
5341
Structural Rating
19
O&M Index
5
O&M Quick
5431
O&M Rating
23
Overall Index
5
Overall Quick
Overall Rating
42
Pipe schematic from manhole 08 0010 to 08 0009
MH: 08 0010MH: 08 0009downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:00AM2 ft. MGO - General Observation - 95% MAG COAT START2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES2 ft. MGO - General Observation - 100% MISSING TILES START6.8 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR14.6 ft. DSZ - Deposits Settled Other, 40 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - MISSING TILES UUNDER FLOW22.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM CORRODED & MISSING33.4 ft. MGO - General Observation - MISSING TILES 5% START48.8 ft. MGO - General Observation - 100% MISSING TILES 1 SECTION64.7 ft. ID - Infiltration Dripper, from 12 to 02 o'clock, within 8 inches of joint: NO106.8 ft. MWM - Water Mark, 90 %of cross sectional area106.8 ft. MGO - General Observation - 60% MAG COAT184.5 ft. MGO - General Observation - 20% MISSING TILES START213.3 ft. MWM - Water Mark, 80 %of cross sectional area228.9 ft. MGO - General Observation - 90% MAG COAT269.3 ft. SRC - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR337.2 ft. MGO - General Observation - 90 5 MAG COAT FINISH337.2 ft. MGO - General Observation - 20% MISSINGTILES FINISH337.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG AREAS OF MISSING TILES337.8 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (12)

  • General Observation - 95% MAG COAT START

    2 ft. - General Observation - 95% MAG COAT START

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES

  • General Observation - 100% MISSING TILES START

    2 ft. - General Observation - 100% MISSING TILES START

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    6.8 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • Deposits Settled Other,  40 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: NO - MISSING TILES UUNDER FLOW

    14.6 ft. - Deposits Settled Other, 40 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: NO - MISSING TILES UUNDER FLOW

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM CORRODED & MISSING

    22.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM CORRODED & MISSING

  • General Observation - MISSING TILES 5% START

    33.4 ft. - General Observation - MISSING TILES 5% START

  • General Observation - 100% MISSING TILES 1 SECTION

    48.8 ft. - General Observation - 100% MISSING TILES 1 SECTION

  • General Observation - 60% MAG COAT

    106.8 ft. - General Observation - 60% MAG COAT

  • General Observation - 20% MISSING TILES START

    184.5 ft. - General Observation - 20% MISSING TILES START

  • General Observation - 90% MAG COAT

    228.9 ft. - General Observation - 90% MAG COAT

  • Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    269.3 ft. - Surface Reinforcement Corroded, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

Observations (22)

DistanceCodeObservation
0MWL
0MWM
228.9MGO90% MAG COAT
2MGO95% MAG COAT START
337.8AMH4:25AM
14.6DSZMISSING TILES UUNDER FLOW
213.3MWM
269.3SRCCIRCUM REBAR
2SAMSEVERE AGG AREAS OF MISSING TILES
337.2MGO90 5 MAG COAT FINISH
0AMH4:00AM
106.8MWM
6.8SRCLONG & CIRCUM REBAR
106.8MGO60% MAG COAT
48.8MGO100% MISSING TILES 1 SECTION
337.2MGO20% MISSINGTILES FINISH
22.6SRCLONG & CIRCUM CORRODED & MISSING
33.4MGOMISSING TILES 5% START
64.7ID
2MGO100% MISSING TILES START
337.2SAMSEVERE AGG AREAS OF MISSING TILES
184.5MGO20% MISSING TILES START

Properties (6)

custom_field_three
CORRODED MISSING LONG & CIRCUM REBAR-95% MAG COAT
custom_field_two
1
customer
LACSD
datetime
2019-04-01T00:59:19-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false