Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2019, 06:54 PM
  • 30 0121_30 0120_3152019_115927.mp4

Date
03/15/2019
W/O
0760336
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00878
PipeID
P17825
Time
11:54 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7942
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
06
Purpose
Capital Improvement Program Assesment
Project
20190315DF_SOUTH_BAY_CITIES_MAIN_TRUNK
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
30 0121
Downstream MH
30 0120
Dir. of Survey
Downstream
Length Surveyed
419.8 ft.
Total Length
419.8 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 30 0121 to 30 0120
MH: 30 0121MH: 30 0120downstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:55 AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.2 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach93.6 ft. MGP - General Photograph262.4 ft. MGP - General Photograph264.5 ft. MGP - General Photograph379 ft. MGP - General Photograph418.2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 80% MAG418.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish419.8 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach419.8 ft. AMH - Downstream Manhole, Survey Ends - 12:20 PM419.8 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)

Observation photos (7)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 80% MAG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - Peeling & Flaking Throughout The Reach

    6.2 ft. - General Observation - Peeling & Flaking Throughout The Reach

  • General Photograph

    93.6 ft. - General Photograph

  • General Photograph

    262.4 ft. - General Photograph

  • General Photograph

    264.5 ft. - General Photograph

  • General Photograph

    379 ft. - General Photograph

Observations (15)

DistanceCodeObservation
418.2SZ80% MAG
418.2SSS
264.5MGP
2SZ80% MAG
0AMH11:55 AM
93.6MGP
419.8MGOPeeling & Flaking Throughout The Reach
2SSS
0MWM
6.2MGOPeeling & Flaking Throughout The Reach
262.4MGP
419.8AMH12:20 PM
419.8MGOGREASE THROUGHOUT THE REACH (5%)
379MGP
0MWL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-03-15T11:54:52-07:00
documentation
FRANKLIN, IGNACIO, RUVALCABA
is_lateral_inspection