Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2019, 09:19 AM
  • 14 0466_14 0465 _03072019_023503.mp4

Date
03/07/2019
W/O
750756
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00580
PipeID
P18555
Time
1:19 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6419
Sewer Name
14 TRUNK "D"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_750756_TV14023_FEB2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0466
Downstream MH
14 0465
Dir. of Survey
Downstream
Length Surveyed
75.2 ft.
Total Length
75.2 ft.
Structural Index
3
Structural Quick
3B2B
Structural Rating
75
O&M Index
3
O&M Quick
513B
O&M Rating
74
Overall Index
3
Overall Quick
Overall Rating
149
Pipe schematic from manhole 14 0466 to 14 0465
MH: 14 0466MH: 14 0465downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 04660 ft. MWL - Water Level, 50 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 75 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start8.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - DEBRIS35.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"75.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish75.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish75.2 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish75.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish75.2 ft. MSA - Survey Abandoned - DUE TO DEBRIS

Observation photos (2)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0AMH14 0466
2.2DAGS
2SSS
75.2SAP
35.5TFC
0MWL
8.7DSZDEBRIS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
75.2SSS
2SAP
75.2DSZ
75.2DAGS
0MWM
75.2MSADUE TO DEBRIS

Properties (6)

additional_info
SC365935
custom_field_two
5
customer
LACSD
datetime
2019-03-07T01:19:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false