Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2019, 09:59 AM
  • 14 0464_14 0463 _03072019_031245.mp4

Date
03/07/2019
W/O
750756
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00580
PipeID
P18553
Time
1:59 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6419
Sewer Name
14 TRUNK "D"
City
LANCASTER
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_750756_TV14023_FEB2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0464
Downstream MH
14 0463
Dir. of Survey
Downstream
Length Surveyed
339.2 ft.
Total Length
339.2 ft.
Structural Index
3
Structural Quick
3M2L
Structural Rating
344
O&M Index
2
O&M Quick
412L
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
482
Pipe schematic from manhole 14 0464 to 14 0463
MH: 14 0464MH: 14 0463downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 04640 ft. MWM - Water Mark, 60 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start31.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"108.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"181.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"206.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"281.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"306.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.8 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES325.8 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES334 ft. H - Hole, at 12 o'clock, within 8 inches of joint: YES337.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish337.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish337.5 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish339.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0463

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Hole, at 12 o'clock, within 8 inches of joint: YES

    316.8 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: YES

    325.8 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES

  • Hole, at 12 o'clock, within 8 inches of joint: YES

    334 ft. - Hole, at 12 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
325.8H
2SSS
229.3TFC
2DAGS
206.7TFC
0AMH14 0464
316.8H
31.1TFC
281.7TFC
337.5DAGS
334H
0MWM
337.5SSS
253.9TFC
108.5TFC
306.1TFC
339.2AMH14 0463
181.4TFC
0MWL
337.5SAP
2SAP

Properties (6)

additional_info
SC365935
custom_field_two
2
customer
LACSD
datetime
2019-03-07T01:59:10-08:00
documentation
PRO PIPE
is_lateral_inspection
false