Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2019, 09:59 AM
  • J 0321A_J 0321_03072019_032436.mp4

Date
03/07/2019
W/O
750732
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00059
PipeID
P11565
Time
1:59 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6465
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
PALOS VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_750732_TV05330_FEB2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
J 0321A
Downstream MH
J 0321
Dir. of Survey
Downstream
Length Surveyed
288 ft.
Total Length
288 ft.
Structural Index
3
Structural Quick
4436
Structural Rating
36
O&M Index
1
O&M Quick
1800
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
44
Pipe schematic from manhole J 0321A to J 0321
MH: J 0321AMH: J 0321downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Begins - J 0321A0 ft. MWL - Water Level, 15 %of cross sectional area20.3 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR25.9 ft. FM - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES25.9 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR41.9 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR77.3 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR77.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES82.4 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR82.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES92.5 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR93 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start122.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish132.9 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR143.6 ft. FM - Fracture Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES143.9 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR154 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES168.5 ft. FS - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start209.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES209.9 ft. FS - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish215 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES220.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES225.9 ft. FH2 - Fracture Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES, Start246.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"284.9 ft. FH2 - Fracture Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish288 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH288 ft. AMH - Downstream Manhole, Survey Ends - J 0321

Observation photos (19)

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    20.3 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    25.9 ft. - Fracture Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    25.9 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    41.9 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    77.3 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    77.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

    82.4 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YESR

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    82.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    92.5 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    93 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    132.9 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Fracture Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

    143.6 ft. - Fracture Multiple, from 07 to 09 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    143.9 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    154 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    168.5 ft. - Fracture Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    209.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    215 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    220.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    225.9 ft. - Fracture Longitudinal Hinge, 2, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (29)

DistanceCodeObservation
77.7CM
0MWM
82.9CL
93CM
154CM
288MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
82.4RFJ
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
288AMHJ 0321
284.9FH2
0AMHJ 0321A
0MWL
77.3RFJ
220.1FM
92.5RFJ
246.8TFA
209.9CM
168.5FS
143.9RFJ
215CM
209.9FS
143.6FM
225.9FH2
25.9FM
122.6CM
132.9RFJ
25.9RFJ
41.9RFJ
20.3RFJ

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-07T01:59:59-08:00
documentation
PROPIPE
is_lateral_inspection
false