Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2019, 07:49 AM
  • F 0025_F 0024_512019_043250.mp4

Date
05/01/2019
W/O
0767445
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10115
Time
12:49 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1191
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20190430MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0025
Downstream MH
F 0024
Dir. of Survey
Downstream
Length Surveyed
474.8 ft.
Total Length
474.8 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
37
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
37
Pipe schematic from manhole F 0025 to F 0024
MH: F 0025MH: F 0024downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR7.6 ft. MGO - General Observation - 69" RCP40.8 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR40.8 ft. SAV - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM72.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR90.3 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR121.1 ft. SRV - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR255.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR455.8 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR474.5 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG474.5 ft. SRC - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR474.5 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Finish - LONG REBAR474.8 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (9)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Aggregate Visible, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - 69" RCP

    7.6 ft. - General Observation - 69" RCP

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    40.8 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

    72.5 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES, Start - LONG REBAR

  • Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    90.3 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    121.1 ft. - Surface Reinforcement Visible, from 12 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

    255.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - CIRCUM REBAR

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

    455.8 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: YES - LONG REBAR

Observations (17)

DistanceCodeObservation
474.5SAMSEVERE AGG
90.3SRCCIRCUM REBAR
474.8AMH5:00AM
40.8SRCCIRCUM REBAR
2SAMSEVERE AGG
0MWL
7.6MGO69" RCP
0MWM
40.8SAVCIRCUM
0AMH4:30AM
72.5SRVLONG REBAR
121.1SRVCIRCUM REBAR
455.8SRVLONG REBAR
474.5SRCCIRCUM REBAR
2SAVCIRCUM REBAR
255.7SRCCIRCUM REBAR
474.5SRVLONG REBAR

Properties (6)

custom_field_three
CIRCUM REBAR CORRODED,LONG REBAR VISIBLE
custom_field_two
1
customer
LACSD
datetime
2019-05-01T00:49:47-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false