Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2019, 07:43 AM
  • F 0027_F 0026_512019_020335.mp4

Date
05/01/2019
W/O
0767445
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10117
Time
12:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1191
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
PARAMOUNT
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20190430MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0027
Downstream MH
F 0026
Dir. of Survey
Downstream
Length Surveyed
542.8 ft.
Total Length
542.8 ft.
Structural Index
5
Structural Quick
5641
Structural Rating
34
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
34
Pipe schematic from manhole F 0027 to F 0026
MH: F 0027MH: F 0026downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:00AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING11.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR11.7 ft. MGO - General Observation - 69" RCP42.4 ft. SRC - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR91 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRORED MISSING REBAR104.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR154.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR540.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN540.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN540.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR CORRODED MISSING BROKEN540.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG542.8 ft. AMH - Downstream Manhole, Survey Ends - 2:30AM

Observation photos (8)

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR CORRODED & MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

    11.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG & CIRCUM REBAR

  • General Observation - 69" RCP

    11.7 ft. - General Observation - 69" RCP

  • Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

    42.4 ft. - Surface Reinforcement Corroded, at 12 o'clock, within 8 inches of joint: NO - LONG REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRORED MISSING REBAR

    91 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CORRORED MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

    104.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    154.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

Observations (17)

DistanceCodeObservation
0AMH2:00AM
540.3MGOConn. @ Mh, 3 O' Clock. OPEN
2SAMSEVERE AGG
91SRCCORRORED MISSING REBAR
11.7SRCLONG & CIRCUM REBAR
540.3MGOConn. @ Mh, 9 O' Clock. OPEN
154.2SRCLONG CIRCUM REBAR
540.3SRCLONG & CIRCUM REBAR CORRODED MISSING BROKEN
0MGOConn. @ Mh, 9 O' Clock. Active
540.3SAMSEVERE AGG
0MWL
2SRCLONG & CIRCUM REBAR CORRODED & MISSING
104.2SRCBROKEN REBAR
11.7MGO69" RCP
42.4SRCLONG REBAR
542.8AMH2:30AM
0MWM

Properties (6)

custom_field_three
LONG & CIRCUM REBAR CORRODED,BROKEN,MISSING
custom_field_two
1
customer
LACSD
datetime
2019-05-01T00:43:27-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false