Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 10, 2019, 07:33 AM
  • Section#1_05 1975_J 0182__4102019__I0127.mp4

Date
04/10/2019
W/O
0764259
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00545
PipeID
P07175
Time
12:33 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0127
Sewer Name
05 9TH STREET CONNECTION TRUNK
City
PALO VERDES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47A
Purpose
Routine Assessment
Project
20190410MDM_9TH_STREET_CONNECTION_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
05 1975
Downstream MH
J 0182
Dir. of Survey
Downstream
Length Surveyed
50.8 ft.
Total Length
50.8 ft.
Structural Index
3
Structural Quick
3721
Structural Rating
23
O&M Index
4
O&M Quick
5242
O&M Rating
24
Overall Index
3
Overall Quick
Overall Rating
47
Pipe schematic from manhole 05 1975 to J 0182
MH: 05 1975MH: J 0182downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:45AM0 ft. MWL - Water Level, 5 %of cross sectional area8.2 ft. MGO - General Observation - 10" VCP12.9 ft. SSS - Surface Spalling, from 08 to 09 o'clock, within 8 inches of joint: YES - SURFACE PEELING17.8 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT17.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT29.2 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - SLIGHT32.8 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start32.8 ft. MWM - Water Mark, 80 %of cross sectional area32.8 ft. MWL - Water Level, 30 %of cross sectional area45.3 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish - SLIGHT45.3 ft. DAGS - Deposits Attached Grease, 20 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish45.3 ft. DAGS - Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start46.1 ft. MGO - General Observation - ZOOM 4' -HIGH FLOW46.1 ft. MWL - Water Level, 60 %of cross sectional area46.1 ft. MWM - Water Mark, 100 %of cross sectional area50.2 ft. DAGS - Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish50.8 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (7)

  • General Observation - 10" VCP

    8.2 ft. - General Observation - 10" VCP

  • Surface Spalling, from 08 to 09 o'clock, within 8 inches of joint: YES - SURFACE PEELING

    12.9 ft. - Surface Spalling, from 08 to 09 o'clock, within 8 inches of joint: YES - SURFACE PEELING

  • Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    17.8 ft. - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    17.8 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Deposits Attached Grease, 20 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    32.8 ft. - Deposits Attached Grease, 20 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    45.3 ft. - Deposits Attached Grease, 25 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ZOOM 4' -HIGH FLOW

    46.1 ft. - General Observation - ZOOM 4' -HIGH FLOW

Observations (19)

DistanceCodeObservation
45.3FLSLIGHT
17.8FLSLIGHT
0MWM
46.1MGOZOOM 4' -HIGH FLOW
32.8DAGS
8.2MGO10" VCP
12.9SSSSURFACE PEELING
32.8MWM
32.8MWL
50.2DAGS
46.1MWL
45.3DAGS
50.8AMH1:20AM
46.1MWM
17.8FLSLIGHT
0AMH12:45AM
29.2FLSLIGHT
0MWL
45.3DAGS

Properties (6)

custom_field_three
SLIGHT FRACTURES JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2019-04-10T00:33:22-07:00
documentation
MARTIN,OLIVER 111,RUVALCABA
is_lateral_inspection