Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2019, 03:28 PM
  • 08 0537_08 0536_482019_085417.mp4

Date
04/08/2019
W/O
0765023
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00021
PipeID
P00599
Time
8:28 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7958
Sewer Name
08 VICTORIA STREET TRUNK
City
COMPTON
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20190408DF_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
08 0537
Downstream MH
08 0536
Dir. of Survey
Downstream
Length Surveyed
281 ft.
Total Length
281 ft.
Structural Index
3
Structural Quick
5131
Structural Rating
12
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 08 0537 to 08 0536
MH: 08 0537MH: 08 0536downstream0 ft. AMH - Upstream Manhole, Survey Begins - 8:32 AM0.1 ft. MWM - Water Mark, 25 %of cross sectional area0.1 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MGO - General Observation - ROACHES @ MH2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.2 ft. MGP - General Photograph16.9 ft. CS - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES, Start32.9 ft. B - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES36.7 ft. CS - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES, Finish67.4 ft. MGP - General Photograph135 ft. MGP - General Photograph277.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish277.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish280 ft. MGO - General Observation - Grease Throughout The Reach (5%)280.1 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach281 ft. AMH - Downstream Manhole, Survey Ends - 9:22 AM

Observation photos (7)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    16.2 ft. - General Photograph

  • Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES, Start

    16.9 ft. - Crack Spiral, from 11 to 12 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 08 to 12 o'clock, within 8 inches of joint: YES

    32.9 ft. - Broken, from 08 to 12 o'clock, within 8 inches of joint: YES

  • General Photograph

    67.4 ft. - General Photograph

  • General Photograph

    135 ft. - General Photograph

Observations (17)

DistanceCodeObservation
277.4SSS
2MGOROACHES @ MH
32.9B
135MGP
280MGOGrease Throughout The Reach (5%)
0AMH8:32 AM
280.1MGOPeeling & Flaking Throughout The Reach
277.4CM
16.2MGP
0.1MWM
36.7CS
6CM
2SSS
67.4MGP
281AMH9:22 AM
0.1MWL
16.9CS

Properties (4)

customer
LACSD
datetime
2019-04-08T08:28:38-07:00
documentation
FRANKLIN, CASTILLO, IGNACIO
is_lateral_inspection