Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2019, 09:03 AM
  • 20 0055_20 0054_03192019_021510.mp4

Date
03/19/2019
W/O
756628
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00742
PipeID
P18976
Time
2:03 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6430
Sewer Name
20 TRUNK "A"
City
PALMDALE
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 20
Page No.
03
Purpose
Routine Assessment
Project
WO_756628_TV20026_MAR2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
20 0055
Downstream MH
20 0054
Dir. of Survey
Downstream
Length Surveyed
344.8 ft.
Total Length
344.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
204
O&M Index
2
O&M Quick
2M00
O&M Rating
136
Overall Index
3
Overall Quick
Overall Rating
340
Pipe schematic from manhole 20 0055 to 20 0054
MH: 20 0055MH: 20 0054downstream0 ft. AMH - Upstream Manhole, Survey Begins - 20 00550 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start343.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish343.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish344.8 ft. AMH - Downstream Manhole, Survey Ends - 20 0054

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2SAV
343.3SAV
0AMH20 0055
344.8AMH20 0054
2DAGS
343.3DAGS
0MWL
0MWM

Properties (6)

additional_info
SC365948
custom_field_two
2
customer
LACSD
datetime
2019-03-19T02:03:30-07:00
documentation
PRO PIPE
is_lateral_inspection