Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2019, 10:49 AM
  • 08 0521_08 0520A_482019_035339.mp4

Date
04/08/2019
W/O
0765023
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00021
PipeID
P25927
Time
3:49 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1177
Sewer Name
08 VICTORIA STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20190408MDM_VICTORIA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0520A
Downstream MH
08 0521
Dir. of Survey
Upstream
Length Surveyed
266.9 ft.
Total Length
266.9 ft.
Structural Index
2
Structural Quick
412D
Structural Rating
56
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
60
Pipe schematic from manhole 08 0520A to 08 0521
MH: 08 0520AMH: 08 0521upstream0 ft. AMH - Upstream Manhole, Survey Ends - 4:30AM0.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0.5 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN5.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - H18.9 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL35 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H35 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H39 ft. FC - Fracture Circumferential, from 10 to 04 o'clock, within 8 inches of joint: YES - SL51.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H59.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL79.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H87.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H91.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H91.9 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H116.2 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H124.4 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL132.5 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - SL144.6 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - H152.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL161 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL165 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - SL169.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL173.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H177.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H185.5 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL189.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H213.9 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - H226.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H230 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE230 ft. MWM - Water Mark, 30 %of cross sectional area238.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT243.7 ft. RPP - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH243.7 ft. RPP - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH253.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open266.9 ft. MWL - Water Level, 10 %of cross sectional area266.9 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active266.9 ft. MWM - Water Mark, 60 %of cross sectional area266.9 ft. AMH - Downstream Manhole, Survey Begins - 3:55AM

Observation photos (2)

  • Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

    23.2 ft. - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

  • Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

    23.2 ft. - Repair Patch, from 02 to 04 o'clock, within 8 inches of joint: YES - CONCRETE PATCH

Observations (38)

DistanceCodeObservation
231.9FCH
266.4MGOConn. @ Mh, 3 O' Clock. Capped
179.1FCH
175FCH
53FCH
97.7FCSL
0MWL
23.2RPPCONCRETE PATCH
105.9FCSL
13.2TFOpen
36.9FMHAIRLINE
40.8FCH
89.6FCH
122.3FCH
114.1FCSL
101.9FCSL
77.5FCH
142.5FCSL
0MGOConn. @ Mh, 9 O' Clock. Active
231.9FCH
134.4FCSL
261.1FCH
227.9FCSL
28.3FCSLIGHT
93.5FCH
23.2RPPCONCRETE PATCH
266.9AMH4:30AM
175FCH
150.7FCH
0MWM
187.5FCH
0AMH3:55AM
81.4FCSL
215.5FCH
36.9MWM
266.4MGOConn. @ Mh, 9 O' Clock. OPEN
207.7FCSL
248FCSL

Properties (7)

additional_info
REVERSE INSPECTION
custom_field_three
SLIGHT FRACTURES -REPAIR PATCH GOOD COND
custom_field_two
3
customer
LACSD
datetime
2019-04-08T03:49:48-07:00
documentation
MARTIN,REVELES,OLIVER 111,RUVALCABA
is_lateral_inspection
false