Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 4, 2019, 06:31 AM
  • 32 1237_32 1236_04032019_235102.mp4

Date
04/03/2019
W/O
756114
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00832
PipeID
P19706
Time
11:31 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6446
Sewer Name
32 BOUQUET CANYON TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
07
Purpose
Routine Assessment
Project
WO_756114_TV32007_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
32 1236
Downstream MH
32 1237
Dir. of Survey
Upstream
Length Surveyed
400.1 ft.
Total Length
400.2 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
2
O&M Quick
2O00
O&M Rating
158
Overall Index
2
Overall Quick
Overall Rating
166
Pipe schematic from manhole 32 1236 to 32 1237
MH: 32 1236MH: 32 1237upstream0 ft. AMH - Upstream Manhole, Survey Ends - 32 12370 ft. MGO - General Observation - ACTIVE CONNECTION OF MH 9 O'CLOCK1.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish23.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"80.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES97.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES177.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES251.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"325.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"398.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start400.1 ft. MWM - Water Mark, 10 %of cross sectional area400.1 ft. MWL - Water Level, 5 %of cross sectional area400.1 ft. AMH - Downstream Manhole, Survey Begins - 32 1236400.1 ft. MGO - General Observation - RUN LIST STATES NRCP. ACTUAL MATERIAL IS VCP. SECTION INFO CHANGED TO REFLECT ACTUAL PIPE MATERIAL.

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    190.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    223.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    319.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
400.1AMH32 1237
223.3CL
2DAGS
222.6TFC
0MWM
400.1MGOACTIVE CONNECTION OF MH 9 O'CLOCK
398.2DAGS
319.7CM
0MWL
74.8TFC
190.7CM
302.5TFC
148.4TFC
0AMH32 1236
377TFC
0MGORUN LIST STATES NRCP. ACTUAL MATERIAL IS VCP. SECTION INFO CHANGED TO REFLECT ACTUAL PIPE MATERIAL.

Properties (6)

additional_info
SC366214
custom_field_two
3
customer
LACSD
datetime
2019-04-03T23:31:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false