Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2019, 08:39 AM
  • 32 1241_32 1240 _04022019_014804.mp4

Date
04/02/2019
W/O
756114
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00832
PipeID
P19710
Time
1:39 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6443
Sewer Name
32 BOUQUET CANYON TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
07
Purpose
Routine Assessment
Project
WO_756114_TV32007_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Rectangular
Height
12 in.
Width
12 in.
Upstream MH
32 1241
Downstream MH
32 1240
Dir. of Survey
Downstream
Length Surveyed
210.7 ft.
Total Length
210.7 ft.
Structural Index
3
Structural Quick
3C22
Structural Rating
70
O&M Index
2
O&M Quick
2C00
O&M Rating
36
Overall Index
3
Overall Quick
Overall Rating
106
Pipe schematic from manhole 32 1241 to 32 1240
MH: 32 1241MH: 32 1240downstream0 ft. MGO - General Observation - RUN LIST STATES NRCP. MATERIAL IS VCP. SECTION INFO CHANGED TO REFLECT ACTUAL PIPE MATERIAL0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 124111.9 ft. CS - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES34 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"74.8 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES96.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES100.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start112.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.3 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start185.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.6 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Finish207.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish210.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK210.7 ft. AMH - Downstream Manhole, Survey Ends - 32 1240

Observation photos (5)

  • Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

    11.9 ft. - Crack Spiral, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    74.8 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    96.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    100.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Other, 5 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES, Start

    113.3 ft. - Deposits Attached Other, 5 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
100.6CM
185.5TFC
0MGORUN LIST STATES NRCP. MATERIAL IS VCP. SECTION INFO CHANGED TO REFLECT ACTUAL PIPE MATERIAL
207.6CM
210.7MGOCONNECTION AT MH 9 O'CLOCK
96.7CM
74.8CL
0MWL
204.6DAZ
210.7AMH32 1240
11.9CS
112.4TFC
113.3DAZ
34TFC
0AMH32 1241

Properties (6)

additional_info
SC366211
custom_field_two
3
customer
LACSD
datetime
2019-04-02T01:39:29-07:00
documentation
PRO PIPE
is_lateral_inspection
false