Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2019, 08:57 AM
  • 05 1095_05 1094_03152019_022745.mp4

Date
03/15/2019
W/O
755956
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00488
PipeID
P06329
Time
1:57 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6477
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_755956_TV05328_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
05 1095
Downstream MH
05 1094
Dir. of Survey
Downstream
Length Surveyed
325.4 ft.
Total Length
325.4 ft.
Structural Index
3
Structural Quick
5144
Structural Rating
38
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
42
Pipe schematic from manhole 05 1095 to 05 1094
MH: 05 1095MH: 05 1094downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 10950 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES19.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES41.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES48 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"49.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES59.2 ft. FS - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES105 ft. CM - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES111.3 ft. FM - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES123.6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES148.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"154.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES163 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start194.6 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES246.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"323.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1094

Observation photos (11)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    3 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    19.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    41.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    49.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

    59.2 ft. - Fracture Spiral, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

    105 ft. - Crack Multiple, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    111.3 ft. - Fracture Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    123.6 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    154.1 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    163 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Broken, from 12 to 04 o'clock, within 8 inches of joint: YES

    194.6 ft. - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
3CL
325.4AMH05 1094
0AMH05 1095
163FM
48TFC
19.2FM
111.3FM
194.6B
59.2FS
0MWM
41.3FM
323.9FM
154.1CM
49.4CM
123.6FL
0MWL
246.8TFC
105CM
148.7TFA

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-15T01:57:50-07:00
documentation
PROPIPE
is_lateral_inspection
false