Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 27, 2019, 05:39 AM
  • 29 0338_29 0337 _03262019_231602.mp4

Date
03/26/2019
W/O
755925
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z01017
PipeID
P24357
Time
10:39 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6499
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_755925_TV29105_MAR2019
Sewer Type
Gravity
Material
CON
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0338
Downstream MH
29 0337
Dir. of Survey
Downstream
Length Surveyed
374.8 ft.
Total Length
374.8 ft.
Structural Index
3
Structural Quick
4632
Structural Rating
34
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
34
Pipe schematic from manhole 29 0338 to 29 0337
MH: 29 0338MH: 29 0337downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 03386 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"42.1 ft. FM - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES59.5 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES89.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS IN LATERAL95.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES165.7 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: YES, 6"172.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES175.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"187.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES192.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start209.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"239.7 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: YES, 6"250.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"266.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish313.2 ft. FM - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES328.5 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES332.7 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"335.1 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: YES, 6"336.4 ft. FM - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES357.8 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: YES, 6"371.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish374.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK374.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0337

Observation photos (9)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    42.1 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    59.5 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    95.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    172.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    187.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    192.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

    313.2 ft. - Fracture Multiple, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

    336.4 ft. - Fracture Multiple, from 03 to 09 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
42.1FM
0MWL
313.2FM
0MGOCONNECTION AT MH 9 O'CLOCK
89.4TFDEBRIS IN LATERAL
209.9TBA
328.5FM
374.8MGOCONNECTION AT MH 9 O'CLOCK
371.7SAP
335.1TFB
332.7TBA
175.9TFA
187.7CL
6SAP
59.5FL
165.7TFB
35TF
95.6CL
172.2FM
0MWM
239.7TFB
250.1TFA
374.8AMH29 0337
336.4FM
192.5FM
0AMH29 0338
266.1FM
357.8TFB

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-03-26T22:39:11-07:00
documentation
PROPIPE
is_lateral_inspection
false