Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 3, 2019, 06:37 AM
  • 15 0108_15 0107 _04022019_235442.mp4

Date
04/02/2019
W/O
755853
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00590
PipeID
P11986
Time
11:37 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5844
Sewer Name
15 ABBEY STREET TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_755853_TV15245_MAR2019
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0108
Downstream MH
15 0107
Dir. of Survey
Downstream
Length Surveyed
157.6 ft.
Total Length
157.6 ft.
Structural Index
4
Structural Quick
5142
Structural Rating
22
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 15 0108 to 15 0107
MH: 15 0108MH: 15 0107downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01080 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.3 ft. CH3 - Crack Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES12.3 ft. FS - Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES15.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start39 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.9 ft. FS - Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES109.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.4 ft. FM - Fracture Multiple, from 12 to 06 o'clock, within 8 inches of joint: YES156.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish156.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish157.6 ft. MGO - General Observation - SERVICE CONNECTION AT 12 O' CLOCK AT MH157.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0107

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES

    6.3 ft. - Crack Longitudinal Hinge, 3, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

    12.3 ft. - Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    15.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    39 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

    64.9 ft. - Fracture Spiral, from 02 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 06 o'clock, within 8 inches of joint: YES

    127.4 ft. - Fracture Multiple, from 12 to 06 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0MWM
157.6MGOSERVICE CONNECTION AT 12 O' CLOCK AT MH
0MWL
39FM
109.1TF
54.7TB
156.9DAGS
2.5DAGS
157.6AMH15 0107
127.4FM
156.8CM
0AMH15 0108
0MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
12.3FS
15.6CM
6.3CH3
42.5FM
64.9FS

Properties (6)

additional_info
SC366081
custom_field_two
2
customer
LACSD
datetime
2019-04-02T23:37:46-07:00
documentation
PROPIPE
is_lateral_inspection
false