Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 27, 2019, 08:51 AM
  • 08 0466_08 0465_2272019_050429.mp4

Date
02/27/2019
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00522
Time
12:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1130
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190226MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0466
Downstream MH
08 0465
Dir. of Survey
Downstream
Length Surveyed
345.8 ft.
Total Length
345.8 ft.
Structural Index
5
Structural Quick
5741
Structural Rating
39
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
43
Pipe schematic from manhole 08 0466 to 08 0465
MH: 08 0466MH: 08 0465downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR2 ft. MGO - General Observation - 50% MISSING TILES START2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG13.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING EBAR25.6 ft. MGO - General Observation - 100% TILLES MISSING35.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR60.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR65.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR111.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR168.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR345.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR345.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active345.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG345.8 ft. AMH - Downstream Manhole, Survey Ends - 5:35AM

Observation photos (9)

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR

  • General Observation - 50% MISSING TILES START

    2 ft. - General Observation - 50% MISSING TILES START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING EBAR

    13.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING EBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR

    35.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    60.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    65.9 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    111.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    168.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

Observations (18)

DistanceCodeObservation
2SRCBROKEN MISSING REBAR - CORRISON BEYOUND REBAR
35.2SRCHANGING REBAR
345.2SRCBROKEN MISSING REBAR - CORRISON BEYOUND REBAR
13.7SRCHANGING EBAR
168.3SRCHANGING REBAR
0MWL
2MGO50% MISSING TILES START
0AMH5:05AM
345.8AMH5:35AM
0MWM
111.7SRCHANGING REBAR
65.9SRCHANGING REBAR
2SAMSEVERE AGG
25.6MGO100% TILLES MISSING
0MGOConn. @ Mh, 3 O' Clock. OPEN
345.2MGOConn. @ Mh, 3 O' Clock. Active
345.2SAMSEVERE AGG
60.7SRCHANGING REBAR

Properties (6)

custom_field_three
BROKEN MISSING REBAR
custom_field_two
1
customer
LACSD
datetime
2019-02-27T00:51:36-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false