Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 27, 2019, 08:50 AM
  • 08 0467_08 0466_2272019_041857.mp4

Date
02/27/2019
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00523
Time
12:50 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1129
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190226MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0467
Downstream MH
08 0466
Dir. of Survey
Downstream
Length Surveyed
157.9 ft.
Total Length
157.9 ft.
Structural Index
5
Structural Quick
5741
Structural Rating
39
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
43
Pipe schematic from manhole 08 0467 to 08 0466
MH: 08 0467MH: 08 0466downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 6 O' Clock. Active2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - 50% MISSING TILES START2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR12.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR32.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR45.4 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR50.7 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR98.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR126.6 ft. MGO - General Observation - 9 ROWS TILES131.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR157.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN157.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG157.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR157.9 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observation photos (9)

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 50% MISSING TILES START

    2 ft. - General Observation - 50% MISSING TILES START

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR - CORRISON BEYOUND  REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    12.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    32.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    45.4 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR

    50.7 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    98.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR

    131.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - HANGING REBAR

Observations (19)

DistanceCodeObservation
0AMH4:30AM
157.3MGOConn. @ Mh, 3 O' Clock. OPEN
45.4SRCHANGING REBAR
131.3SRCHANGING REBAR
2SAMSEVERE AGG
12.2SRCHANGING REBAR
126.6MGO9 ROWS TILES
0MWL
157.3SAMSEVERE AGG
0MGOConn. @ Mh, 3 O' Clock. OPEN
0MWM
98.5SRCHANGING REBAR
2MGO50% MISSING TILES START
32.6SRCHANGING REBAR
2SRCBROKEN MISSING REBAR - CORRISON BEYOUND REBAR
0MGOConn. @ Mh, 6 O' Clock. Active
157.3SRCBROKEN MISSING REBAR - CORRISON BEYOUND REBAR
157.9AMH4:55AM
50.7SRCHANGING REBAR

Properties (6)

custom_field_three
BROKEN MISSING REBAR
custom_field_two
1
customer
LACSD
datetime
2019-02-27T00:50:23-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false