Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 27, 2019, 08:45 AM
  • 08 0468_08 0467_2272019_022242.mp4

Date
02/27/2019
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00524
Time
12:45 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1129
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190226MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0468
Downstream MH
08 0467
Dir. of Survey
Downstream
Length Surveyed
442.8 ft.
Total Length
442.8 ft.
Structural Index
5
Structural Quick
5A41
Structural Rating
59
O&M Index
5
O&M Quick
5241
O&M Rating
14
Overall Index
5
Overall Quick
Overall Rating
73
Pipe schematic from manhole 08 0468 to 08 0467
MH: 08 0468MH: 08 0467downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 2:20AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Capped0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BEYOUN0 REBAR2 ft. MGO - General Observation - 50% MISSING TILES START4 ft. DSZ - Deposits Settled Other, 70 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - MISSING TILES UNDER FLOW59.2 ft. MGO - General Observation - 100% MISSING TILES73.2 ft. MGO - General Observation - 30% MISSING TILES88 ft. MGO - General Observation - 100% MISSING TILES105.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR131.7 ft. MGO - General Observation - BROKEN REBAR146.8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR174.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR195.9 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR196.9 ft. MGP - General Photograph204.5 ft. MGO - General Observation - 10% MISSING TILES219 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR219 ft. MGO - General Observation - 100% MISSING TILES225.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR229.6 ft. MWM - Water Mark, 60 %of cross sectional area229.6 ft. MWL - Water Level, 40 %of cross sectional area256 ft. MGO - General Observation - 20% MISSING TILES273.3 ft. MGO - General Observation - 80% MISSING TILES287.3 ft. MGO - General Observation - 100% MISSING TILES320.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - HANGING REBAR336.6 ft. MGO - General Observation - 8 ROWS TILES350.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR359.3 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR393.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR442.3 ft. MGO - General Observation - Conn. @ Mh, 12 O' Clock. OPEN442.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR442.3 ft. SAM - Surface Aggregate Missing, from 9 to 03o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG442.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active442.8 ft. AMH - Downstream Manhole, Survey Ends - 3:10AM

Observation photos (21)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BEYOUN0 REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BEYOUN0 REBAR

  • General Observation - 50% MISSING TILES START

    2 ft. - General Observation - 50% MISSING TILES START

  • Deposits Settled Other,  70 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: NO - MISSING TILES UNDER FLOW

    4 ft. - Deposits Settled Other, 70 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: NO - MISSING TILES UNDER FLOW

  • General Observation - 100% MISSING TILES

    59.2 ft. - General Observation - 100% MISSING TILES

  • General Observation - 30% MISSING TILES

    73.2 ft. - General Observation - 30% MISSING TILES

  • General Observation - 100% MISSING TILES

    88 ft. - General Observation - 100% MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    105.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Observation - BROKEN REBAR

    131.7 ft. - General Observation - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

    146.8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    174.5 ft. - Surface Reinforcement Corroded, from 10 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    195.9 ft. - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Photograph

    196.9 ft. - General Photograph

  • General Observation - 10% MISSING TILES

    204.5 ft. - General Observation - 10% MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    219 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    225.5 ft. - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Water Mark, 60 %of cross sectional area

    229.6 ft. - Water Mark, 60 %of cross sectional area

  • Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - HANGING REBAR

    320.8 ft. - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    350.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

    359.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

    393.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - HANGING REBAR

Observations (37)

DistanceCodeObservation
442.8AMH3:10AM
204.5MGO10% MISSING TILES
0MGOConn. @ Mh, 3 O' Clock. Active
174.5SRCBROKEN REBAR
442.3MGOConn. @ Mh, 12 O' Clock. OPEN
4DSZMISSING TILES UNDER FLOW
393.5SRCHANGING REBAR
105.8SRCBROKEN REBAR
0AMH2:20AM
2SAMSEVERE AGG
320.8SRCHANGING REBAR
73.2MGO30% MISSING TILES
442.3SRCBROKEN MISSING REBAR - CORRISON BEYOUND REBAR
195.9SRCBROKEN REBAR
0MGOConn. @ Mh, 3 O' Clock. Capped
219SRCBROKEN REBAR
2SRCBROKEN MISSING REBAR CORRISON BEYOUN0 REBAR
88MGO100% MISSING TILES
359.3SRCCORRISON BEYOUND REBAR
219MGO100% MISSING TILES
131.7MGOBROKEN REBAR
442.3SAMSEVERE AGG
146.8SRCBROKEN REBAR
59.2MGO100% MISSING TILES
350.6SRCHANGING REBAR
256MGO20% MISSING TILES
0MWL
287.3MGO100% MISSING TILES
273.3MGO80% MISSING TILES
336.6MGO8 ROWS TILES
2MGO50% MISSING TILES START
442.3MGOConn. @ Mh, 3 O' Clock. Active
0MWM
225.5SRCBROKEN REBAR
229.6MWM
229.6MWL
196.9MGP

Properties (6)

custom_field_three
BROKEN MISSING REBAR
custom_field_two
1
customer
LACSD
datetime
2019-02-27T00:45:36-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false