Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 27, 2019, 08:35 AM
  • 08 0469_08 0468_2272019_012832.mp4

Date
02/27/2019
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00525
Time
12:35 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1129
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190226MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0469
Downstream MH
08 0468
Dir. of Survey
Downstream
Length Surveyed
436.7 ft.
Total Length
436.7 ft.
Structural Index
5
Structural Quick
5441
Structural Rating
24
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
29
Pipe schematic from manhole 08 0469 to 08 0468
MH: 08 0469MH: 08 0468downstream0 ft. MWL - Water Level, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. MGO - General Observation - 50% MISSING TILES2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR-CORRISON BEYOUND REBAR27.1 ft. MGO - General Observation - 70% MISSING TILES56.2 ft. MGO - General Observation - 50% MISSING TILES111.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR COEEISON BEYOUND REBAR152.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING171.9 ft. MGO - General Observation - 70% MISSING TILES186.8 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR436.4 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG436.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR - CORRISON BEYOUND REBAR436.7 ft. AMH - Downstream Manhole, Survey Ends - 2:10AM

Observation photos (7)

  • General Observation - 50% MISSING TILES

    2 ft. - General Observation - 50% MISSING TILES

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR-CORRISON BEYOUND REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR-CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR COEEISON BEYOUND REBAR

    111.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - MISSING REBAR COEEISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING

    152.3 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR HANGING

  • General Observation - 70% MISSING TILES

    171.9 ft. - General Observation - 70% MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    186.8 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

Observations (15)

DistanceCodeObservation
152.3SRCBROKEN REBAR HANGING
171.9MGO70% MISSING TILES
2MGO50% MISSING TILES
111.2SRCMISSING REBAR COEEISON BEYOUND REBAR
0MWL
436.4SAMSEVERE AGG
0AMH1:30AM
186.8SRCBROKEN REBAR
436.7AMH2:10AM
27.1MGO70% MISSING TILES
2SAMSEVERE AGG
0MWM
436.4SRCBROKEN MISSING REBAR - CORRISON BEYOUND REBAR
56.2MGO50% MISSING TILES
2SRCBROKEN MISSING REBAR-CORRISON BEYOUND REBAR

Properties (6)

custom_field_three
BROKEN MISSING REBAR
custom_field_two
1
customer
LACSD
datetime
2019-02-27T00:35:23-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false