Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2019, 08:53 AM
  • 08 0470_08 0469_2262019_035551.mp4

Date
02/26/2019
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00526
Time
12:53 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1128
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20190226MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0470
Downstream MH
08 0469
Dir. of Survey
Downstream
Length Surveyed
438.7 ft.
Total Length
438.7 ft.
Structural Index
5
Structural Quick
5A41
Structural Rating
54
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
59
Pipe schematic from manhole 08 0470 to 08 0469
MH: 08 0470MH: 08 0469downstream0 ft. MWL - Water Level, 60 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 6 O' Clock. OPEN0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. MGO - General Observation - 100% MISSING TILES2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG16.2 ft. MGO - General Observation - 3 ROWS TILE INPLACE26.2 ft. MGO - General Observation - 60% MAG COAT26.2 ft. MGO - General Observation - 10% MISSING TILES33.6 ft. MGO - General Observation - 100% MISSING TILES49 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BSYOUND REBAR107.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR111.7 ft. MGO - General Observation - 30% MISSING TILES150.1 ft. MGO - General Observation - 20% MISSING TILES229.9 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR235.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND EBAR235.2 ft. MGO - General Observation - 50% MISSING TILES276.5 ft. MGO - General Observation - 100$ MISSING TILES281.4 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR293.9 ft. MGO - General Observation - 4 ROWS TILES310.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR334 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR341 ft. MGO - General Observation - 25% MISSING TILES355.6 ft. MGO - General Observation - 100% MISSING TILES373.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR391.6 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR421.5 ft. MGO - General Observation - 4 ROWS TILES438.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR438.3 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG438.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR CORRISON BEYOUND REBAR438.7 ft. AMH - Downstream Manhole, Survey Ends - 5:35AM

Observation photos (14)

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - 60% MAG COAT

    26.2 ft. - General Observation - 60% MAG COAT

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BSYOUND REBAR

    49 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BSYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    107.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Observation - 20% MISSING TILES

    150.1 ft. - General Observation - 20% MISSING TILES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

    229.9 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND EBAR

    235.2 ft. - Surface Reinforcement Corroded, from 10 to 12 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND EBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    281.4 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    310.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    334 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • General Observation - 25% MISSING TILES

    341 ft. - General Observation - 25% MISSING TILES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    373.1 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    391.6 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR

Observations (33)

DistanceCodeObservation
26.2MGO60% MAG COAT
235.2SRCCORRISON BEYOUND EBAR
438.3SRCLONG & CIRCUM REBAR
0MWL
26.2MGO10% MISSING TILES
276.5MGO100$ MISSING TILES
0AMH4:40AM
2MGO100% MISSING TILES
33.6MGO100% MISSING TILES
235.2MGO50% MISSING TILES
2SRCLONG & CIRCUM REBAR
150.1MGO20% MISSING TILES
107.2SRCBROKEN REBAR
111.7MGO30% MISSING TILES
293.9MGO4 ROWS TILES
0MWM
373.1SRCBROKEN REBAR
391.6SRCBROKEN REBAR
2SAMSEVERE AGG
310.6SRCBROKEN REBAR
229.9SRVBROKEN REBAR
421.5MGO4 ROWS TILES
438.3SAMSEVERE AGG
0MGOConn. @ Mh, 6 O' Clock. OPEN
341MGO25% MISSING TILES
438.7AMH5:35AM
49SRCBROKEN MISSING REBAR CORRISON BSYOUND REBAR
438.3SRCBROKEN MISSING REBAR CORRISON BEYOUND REBAR
281.4SRCBROKEN MISSING REBAR
355.6MGO100% MISSING TILES
0MGOConn. @ Mh, 3 O' Clock. Active
16.2MGO3 ROWS TILE INPLACE
334SRCBROKEN REBAR

Properties (6)

custom_field_three
CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2019-02-26T00:53:18-08:00
documentation
MARTIN,OLIVER 111,CASTILLO
is_lateral_inspection
false