Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 28, 2018, 08:40 AM
  • 05 0918_05 0917 _12282018_005058.mp4

Date
12/28/2018
W/O
740636
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00547
PipeID
P06149
Time
12:40 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6306
Sewer Name
05 120TH STREET EXTENSION TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
12
Purpose
Routine Assessment
Project
WO_740636_TV05004_DEC2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0917
Downstream MH
05 0918
Dir. of Survey
Upstream
Length Surveyed
311.4 ft.
Total Length
311.4 ft.
Structural Index
3
Structural Quick
3K2I
Structural Rating
290
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
290
Pipe schematic from manhole 05 0917 to 05 0918
MH: 05 0917MH: 05 0918upstream0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 09180 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish258.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start308.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start311.4 ft. MWM - Water Mark, 20 %of cross sectional area311.4 ft. MWL - Water Level, 15 %of cross sectional area311.4 ft. AMH - Downstream Manhole, Survey Begins - 05 0917

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    52.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
311.4SAV
311.4AMH05 0918
0MWL
311.4SSS
52.5SSS
0AMH05 0917
2.7SAV

Properties (6)

additional_info
SC365490
custom_field_two
2
customer
LACSD
datetime
2018-12-28T00:40:42-08:00
documentation
PROPIPE
is_lateral_inspection
false