Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 9, 2019, 11:00 AM
  • F 0263_F 0262 _01092019_030628.mp4

Date
01/09/2019
W/O
740348
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00040
PipeID
P10216
Time
3:00 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6320
Sewer Name
F JOINT OUTFALL F - UNIT 4 RELIEF
City
NORWALK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
WO_740348_TV02272_DEC2018
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Width
39 in.
Upstream MH
F 0263
Downstream MH
F 0262
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole F 0263 to F 0262
MH: F 0263MH: F 0262downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - F 02630 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. MSA - Survey Abandoned - DOWN LEG OF THE U/S SIPHON

Observation photos (3)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - DOWN LEG OF THE U/S SIPHON

    2.1 ft. - Survey Abandoned - DOWN LEG OF THE U/S SIPHON

Observations (6)

DistanceCodeObservation
0MWM
2.1SRV
0AMHF 0263
2.1SAP
0MWL
2.1MSADOWN LEG OF THE U/S SIPHON

Properties (7)

additional_info
SC365754
custom_field_two
2
customer
LACSD
datetime
2019-01-09T03:00:57-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
31219