Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2018, 06:09 AM
  • 05 0190_05 0189 _10312018_222145.mp4

Date
10/31/2018
W/O
735493
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05482
Time
11:09 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6207
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
06
Purpose
Routine Assessment
Project
WO_735493_TV05228_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0190
Downstream MH
05 0189
Dir. of Survey
Downstream
Length Surveyed
322.8 ft.
Total Length
322.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 05 0190 to 05 0189
MH: 05 0190MH: 05 0189downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH0 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 05 01900 ft. MWL - Water Level, 15 %of cross sectional area43.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"194.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"240 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"242.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"291.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.1 ft. RML - Roots Medium Lateral, at 02 o'clock, 20 %, within 8 inches of joint: NO297.3 ft. RMC - Roots Medium Connection, from 08 to 11 o'clock, 20 %, within 8 inches of joint: NO297.3 ft. RBL - Roots Ball Lateral, at 10 o'clock, 75 %297.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"300.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"322.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0189

Observations (23)

DistanceCodeObservation
98.2TF
240TF
300.4TF
291.1TF
0MWM
0MGOCAPPED LATERAL 9 O'CLOCK @ MH
297.3RMC
191.8TF
0MGOCAPPED LATERAL 3 O'CLOCK @ MH
0AMH05 0190
43.7TF
297.3RBL
291.1RML
143.2TF
285.8TF
297.3TF
322.8AMH05 0189
194.4TF
65.4TF
242.8TF
107.8TF
0MWL
46.7TF

Properties (7)

additional_info
SC365235
custom_field_two
4
customer
LACSD
datetime
2018-10-31T23:09:55-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP