Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2018, 05:52 AM
  • 05 0191_05 0190 _10312018_220924.mp4

Date
10/31/2018
W/O
735493
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05483
Time
10:52 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6207
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
06
Purpose
Routine Assessment
Project
WO_735493_TV05228_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0191
Downstream MH
05 0190
Dir. of Survey
Downstream
Length Surveyed
352 ft.
Total Length
352 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole 05 0191 to 05 0190
MH: 05 0191MH: 05 0190downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 01915.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"38 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.2 ft. RFC - Roots Fine Connection, at 10 o'clock231.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"310.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"313.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"326 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"352 ft. AMH - Downstream Manhole, Survey Ends - 05 0190352 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH352 ft. MGO - General Observation - CAPPED LATERAL 3 O'CLOCK @ MH

Observations (23)

DistanceCodeObservation
112.2TF
352AMH05 0190
147.8TF
224.2TF
185.8TF
171.2TF
224.2RFC
231.8TF
352MGOCAPPED LATERAL 9 O'CLOCK @ MH
0MWL
328.6TF
68.8TF
313.8TF
326TF
267.5TF
352MGOCAPPED LATERAL 3 O'CLOCK @ MH
0MWM
247.1TF
310.9TF
150.5TF
0AMH05 0191
38TF
5.3TF

Properties (7)

additional_info
SC365235
custom_field_two
4
customer
LACSD
datetime
2018-10-31T22:52:51-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP