Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2019, 10:05 AM
  • 02 1843_02 1842_01222019_022721.mpg

Date
01/22/2019
W/O
745532
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00283
PipeID
P04188
Time
2:05 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5341
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
RIFR_WO_745532_TV02213_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
02 1843
Downstream MH
02 1842
Dir. of Survey
Downstream
Length Surveyed
512.5 ft.
Total Length
512.6 ft.
Structural Index
5
Structural Quick
5S00
Structural Rating
505
O&M Index
2
O&M Quick
4121
O&M Rating
7
Overall Index
5
Overall Quick
Overall Rating
512
Pipe schematic from manhole 02 1843 to 02 1842
MH: 02 1843MH: 02 1842downstream0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 18430.1 ft. MWM - Water Mark, 50 %of cross sectional area2.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 8"2.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13 ft. LR - Alignment Right, 15 %167.5 ft. LL - Alignment Left, 10 %506.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish512.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1842

Observation photos (1)

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
512.6AMH02 1842
13LR
0MWL
0AMH02 1843
2.3TFA
167.5LL
2.3SRV
506.7SRV
0.1MWM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-01-22T02:05:53-08:00
documentation
PROPIPE
is_lateral_inspection
false