Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2019, 07:14 AM
  • 02 2093_02 2092_01212019_233827.mpg

Date
01/21/2019
W/O
745532
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00283
PipeID
P04194
Time
11:14 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5341
Sewer Name
02 MONTEBELLO INTERCEPTOR TRUNK, SECTS 1&2
City
COMMERCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
18
Purpose
Routine Assessment
Project
RIFR_WO_745532_TV02213_JAN2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
02 2093
Downstream MH
02 2092
Dir. of Survey
Downstream
Length Surveyed
477.9 ft.
Total Length
477.9 ft.
Structural Index
3
Structural Quick
3R21
Structural Rating
284
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
289
Pipe schematic from manhole 02 2093 to 02 2092
MH: 02 2093MH: 02 2092downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 20930 ft. MWL - Water Level, 75 %of cross sectional area0 ft. MWM - Water Mark, 80 %of cross sectional area6.6 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start72.3 ft. MGO - General Observation - MAG COATING THROUGHOUT196.3 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area476.1 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish477.9 ft. AMH - Downstream Manhole, Survey Ends - 02 2092

Observation photos (1)

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
196.3MWLS
0AMH02 2093
477.9AMH02 2092
0MWL
0MWM
476.1SAP
72.3MGOMAG COATING THROUGHOUT
6.6SAP

Properties (6)

custom_field_two
2
customer
LACSD
datetime
2019-01-21T23:14:44-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30160