Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2019, 05:44 AM
  • H 0470_H 0469 _01092019_215255.mp4

Date
01/09/2019
W/O
740185
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00179
PipeID
P10867
Time
9:44 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6297
Sewer Name
H JOINT OUTFALL H - UNIT 5C
City
EL MONTE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_740185_TV15163_DEC2018
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0469
Downstream MH
H 0470
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole H 0469 to H 0470
MH: H 0469MH: H 0470upstream0 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.0 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES2 ft. AMH - Downstream Manhole, Survey Begins - H 04692 ft. MWL - Water Level, 40 %of cross sectional area2 ft. MWM - Water Mark, 40 %of cross sectional area

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (6)

DistanceCodeObservation
0AMHH 0469
0MWL
2SAP
0MWM
2MSAVIEW OF UPLEG OF D/S SIPHON.
2SSS

Properties (6)