Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 27, 2018, 09:14 AM
  • 22 0440_22 0439 _12272018_012833.mp4

Date
12/27/2018
W/O
740124
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00815
PipeID
P16777
Time
1:14 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6305
Sewer Name
22 LARK ELLEN TRUNK, SECTS 2&3
City
COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_740124_TV22047_DEC2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0440
Downstream MH
22 0439
Dir. of Survey
Downstream
Length Surveyed
364.8 ft.
Total Length
364.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
216
Pipe schematic from manhole 22 0440 to 22 0439
MH: 22 0440MH: 22 0439downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 04400 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"26.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"120.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"173.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"222 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"279 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"323.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"327.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"364.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish364.8 ft. AMH - Downstream Manhole, Survey Ends - 22 0439

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0AMH22 0440
124.6TFC
22.7TFC
2.6SAV
169.1TF
120.1TFC
279TFC
26.6TFC
327.8TFC
0MWM
364.8SAV
323.5TFC
173.2TF
274.9TFC
75.7TF
0MWL
222TF
364.8AMH22 0439
71.5TFC
226.3TFC

Properties (6)

additional_info
SC365489
custom_field_two
3
customer
LACSD
datetime
2018-12-27T01:14:19-08:00
documentation
PROPIPE
is_lateral_inspection
false