Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2019, 07:08 PM
  • C 0311A _C 0311_252019_111424.mp4

Date
02/05/2019
W/O
0753893
Weather
Heavy Rain
Operator/Surveyor
FRANKLIN
Sewer ID
Z00135
PipeID
P09772
Time
11:08 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7910
Sewer Name
C JOINT OUTFALL C - UNIT 6F
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
04
Purpose
Capital Improvement Program Assesment
Project
20190205DF_JOINT_OUTFALL_C_UNIT_6F
Material
Reinforced Concrete Pipe
Shape
Circular
Height
15 in.
Upstream MH
C 0311
Downstream MH
C 0311A
Dir. of Survey
Upstream
Length Surveyed
160.4 ft.
Total Length
160.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole C 0311 to C 0311A
MH: C 0311MH: C 0311Aupstream0 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach0 ft. AMH - Downstream Manhole, Survey Ends - 11:36 AM0 ft. MGO - General Observation - Grease Throughout The Reach (5%)0.6 ft. MGP - General Photograph0.6 ft. MGP - General Photograph0.6 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG0.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0.6 ft. MGP - General Photograph0.6 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES1.4 ft. MGO - General Observation - ROACHES @ MH1.6 ft. MGP - General Photograph63.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.7 ft. MGP - General Photograph109.4 ft. MGP - General Photograph158.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start158.4 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 85% MAG160.3 ft. MGP - General Photograph160.4 ft. MWM - Water Mark, 20 %of cross sectional area160.4 ft. MWL - Water Level, 15 %of cross sectional area160.4 ft. AMH - Upstream Manhole, Survey Begins - 10:12 AM

Observation photos (10)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 85% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 85% MAG

  • General Photograph

    51 ft. - General Photograph

  • General Photograph

    82.7 ft. - General Photograph

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    97 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    158.8 ft. - General Photograph

  • General Photograph

    159.8 ft. - General Photograph

  • General Photograph

    159.8 ft. - General Photograph

  • General Photograph

    159.8 ft. - General Photograph

  • Deposits Attached Encrustation, 20 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    159.8 ft. - Deposits Attached Encrustation, 20 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
160.4MGOPeeling & Flaking Throughout The Reach
82.7MGP
159.8MGP
0.1MGP
160.4AMH11:36 AM
0MWM
160.4MGOGrease Throughout The Reach (5%)
159.8MGP
159.8SZ65% MAG
0MWL
97SSS
2SAV
158.8MGP
159MGOROACHES @ MH
159.8SAV
0AMH10:12 AM
159.8SSS
51MGP
2SZ85% MAG
159.8MGP
159.8DAE

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-02-05T11:08:24-08:00
documentation
FRANKLIN, IGNACIO, RUVALCABA
is_lateral_inspection
false