Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2019, 12:16 PM
  • Section#9_18 1043_18 1042__242019__I0117.mp4

Date
02/04/2019
W/O
0753099
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00678
PipeID
P14897
Time
4:16 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0117
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 2A
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20190201MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
18 1043
Downstream MH
18 1042
Dir. of Survey
Downstream
Length Surveyed
149.8 ft.
Total Length
149.8 ft.
Structural Index
2
Structural Quick
412A
Structural Rating
26
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
28
Pipe schematic from manhole 18 1043 to 18 1042
MH: 18 1043MH: 18 1042downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - ACTIVE MH CONN 3:000 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM8.6 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SL8.6 ft. FC - Fracture Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES - SLIGHT12.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - HAIRLINE21.5 ft. MGO - General Observation - 10" VCP32.7 ft. FC - Fracture Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES - SL52.6 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL61.4 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - SLUDGE61.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN63.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL71.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL71.2 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - H79 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H79 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - H95 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL118.7 ft. FC - Fracture Circumferential, from 08 to 03 o'clock, within 8 inches of joint: YES - SL119.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN149 ft. MGO - General Observation - ACTIVE MH CONN 12:00149.8 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (2)

  • General Observation - 10" VCP

    21.5 ft. - General Observation - 10" VCP

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    63.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

Observations (22)

DistanceCodeObservation
0MWL
79FCH
52.6FCSL
32.7FCSL
149MGOACTIVE MH CONN 12:00
8.6FCSL
79FCH
0MGOACTIVE MH CONN 3:00
12.9FCHAIRLINE
0MWM
71.2FCSL
119.7TFOPEN
61.4DSZSLUDGE
8.6FCSLIGHT
118.7FCSL
63.1FMSL
149.8AMH5:10AM
95FCSL
61.4TFOPEN
21.5MGO10" VCP
71.2FCH
0AMH4:45AM

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2019-02-04T04:16:28-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false