Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 4, 2019, 10:47 AM
  • Section#7_18 041_18 1040__242019__I0117.mp4

Date
02/04/2019
W/O
0753099
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00678
PipeID
P14895
Time
2:47 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0117
Sewer Name
18 LA HABRA HEIGHTS TRUNK, SECTION 2A
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20190201MDM_LA_HABRA_HEIGHTS_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
18 1040
Downstream MH
18 1041
Dir. of Survey
Upstream
Length Surveyed
219.4 ft.
Total Length
219.4 ft.
Structural Index
2
Structural Quick
3326
Structural Rating
21
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
21
Pipe schematic from manhole 18 1040 to 18 1041
MH: 18 1040MH: 18 1041upstream0 ft. AMH - Upstream Manhole, Survey Ends - 3:30AM4.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL4.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL47.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN64.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL64.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL77.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN91 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL123.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - SL123.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN145.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN145.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL179.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN185.8 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES - SL193.7 ft. MGO - General Observation - 10" VCP201.7 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SLIGHT219.4 ft. MWM - Water Mark, 30 %of cross sectional area219.4 ft. MWL - Water Level, 5 %of cross sectional area219.4 ft. AMH - Downstream Manhole, Survey Begins - 3:00AM

Observation photos (1)

  • General Observation - 10" VCP

    25.7 ft. - General Observation - 10" VCP

Observations (19)

DistanceCodeObservation
39.8TFOPEN
154.7FCSL
0MWM
96.1FLSL
172.2TFOPEN
219.4AMH3:30AM
25.7MGO10" VCP
128.4FCSL
74.1TFOPEN
0MWL
33.6FLSL
154.7FCSL
215FCSL
96.1TFOPEN
0AMH3:00AM
74.1FLSL
142TFOPEN
17.7FCSLIGHT
215FCSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2019-02-04T02:47:53-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false