Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 26, 2018, 09:49 AM
  • H 1360_H 1359 _11262018_022029.mp4

Date
11/26/2018
W/O
735502
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01187
PipeID
P26157
Time
1:49 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6204
Sewer Name
H JOINT OUTFALL H - UNIT 5D RELIEF
City
EL MONTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
WO_735502_TV15242_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 1360
Downstream MH
H 1359
Dir. of Survey
Downstream
Length Surveyed
402.8 ft.
Total Length
402.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2_00
O&M Rating
320
Overall Index
2
Overall Quick
Overall Rating
320
Pipe schematic from manhole H 1360 to H 1359
MH: H 1360MH: H 1359downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 13602 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start400.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish400.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish402.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK402.8 ft. AMH - Downstream Manhole, Survey Ends - H 1359

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2DAE
0MWM
400.2DAE
2DAGS
402.8MGOACTIVE CONNECTION AT MH 3 O'CLOCK
400.6DAGS
0MWL
0AMHH 1360
402.8AMHH 1359

Properties (7)

additional_info
SC365370
custom_field_two
4
customer
LACSD
datetime
2018-11-26T01:49:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
40073