Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2018, 10:18 AM
  • H 1491_H 1490 _12032018_023936.mp4

Date
12/03/2018
W/O
735025
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01206
PipeID
P16451
Time
2:18 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6241
Sewer Name
H JOINT OUTFALL H - UNIT 8M RELIEF
City
WEST COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
30
Purpose
Routine Assessment
Project
WO_735025_TV22148_NOV2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 1491
Downstream MH
H 1490
Dir. of Survey
Downstream
Length Surveyed
627 ft.
Total Length
627 ft.
Structural Index
3
Structural Quick
3W00
Structural Rating
366
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
366
Pipe schematic from manhole H 1491 to H 1490
MH: H 1491MH: H 1490downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 14910 ft. MWM - Water Mark, 30 %of cross sectional area14.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.6 ft. MGO - General Observation - MAG COAT531.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"621.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start621.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish626.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish627 ft. MSA - Survey Abandoned - FLOW WENT UP CAM HITTING TOP OF PIPE

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    14.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

    621.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observations (10)

DistanceCodeObservation
14.6SAV
0MWL
14.6MGOMAG COAT
627MSAFLOW WENT UP CAM HITTING TOP OF PIPE
621.9SAV
621.8SAP
0AMHH 1491
531.5TF
0MWM
626.9SAP

Properties (6)

additional_info
SC365469
custom_field_two
5
customer
LACSD
datetime
2018-12-03T02:18:17-08:00
documentation
PROPIPE
is_lateral_inspection
false