Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2018, 11:15 AM
  • 05 0353_05 0352 _11202018_034122.mp4

Date
11/20/2018
W/O
735027
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05567
Time
3:15 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6226
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_735027_TV05325_NOV2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
05 0353
Downstream MH
05 0352
Dir. of Survey
Downstream
Length Surveyed
440.2 ft.
Total Length
440.2 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
261
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
261
Pipe schematic from manhole 05 0353 to 05 0352
MH: 05 0353MH: 05 0352downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 03530.1 ft. MWM - Water Mark, 35 %of cross sectional area2.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start435.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish440.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0352

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
435.9SAP
0MWL
2.1MGOMAG COAT
2.1SAP
0MGOCONNECTION AT MH 3 O'CLOCK
440.2AMH05 0352
0.1MWM
0AMH05 0353