Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2018, 09:56 AM
  • 05 0344_05 0343 _11202018_023717.mp4

Date
11/20/2018
W/O
735027
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00432
PipeID
P05558
Time
1:56 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6226
Sewer Name
05 DISTRICT #5 MAIN RELIEF TRUNK
City
LAWNDALE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_735027_TV05325_NOV2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
05 0344
Downstream MH
05 0343
Dir. of Survey
Downstream
Length Surveyed
484.8 ft.
Total Length
484.8 ft.
Structural Index
3
Structural Quick
513R
Structural Rating
293
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
293
Pipe schematic from manhole 05 0344 to 05 0343
MH: 05 0344MH: 05 0343downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 03440 ft. MWL - Water Level, 15 %of cross sectional area2.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start314.9 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO484.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish484.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0343 ZOOMED IN

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

    314.9 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO

Observations (7)

DistanceCodeObservation
2.9SAP
0MWM
0AMH05 0344
314.9SRV
484.8AMH05 0343 ZOOMED IN
484.5SAP
0MWL

Properties (6)

additional_info
SC365454
custom_field_two
2
customer
LACSD
datetime
2018-11-20T01:56:39-08:00
documentation
PROPIPE
is_lateral_inspection
false