Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2019, 05:36 PM
  • B 0017_B 0016_1292019_101121.mp4

Date
01/29/2019
W/O
0734335
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00072
PipeID
P08527
Time
9:36 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7906
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20190128DF_JOINT_OUTFALL_B_UNIT_1A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
120 in.
Upstream MH
B 0017
Downstream MH
B 0016
Dir. of Survey
Downstream
Length Surveyed
562 ft.
Total Length
562 ft.
Structural Index
4
Structural Quick
5232
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole B 0017 to B 0016
MH: B 0017MH: B 0016downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:45 AM0.1 ft. MWM - Water Mark, 15 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 30% MAG10.6 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.5 ft. MGP - General Photograph66.1 ft. MGP - General Photograph147.2 ft. MGP - General Photograph214 ft. MGP - General Photograph357.7 ft. MGP - General Photograph560.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish560.2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 30% MAG560.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish560.2 ft. SRC - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish560.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish560.2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish561 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)561 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach562 ft. MSA - Survey Abandoned - FLOAT FLIPPED

Observation photos (10)

  • Upstream Manhole, Survey Begins - 8:45 AM

    0 ft. - Upstream Manhole, Survey Begins - 8:45 AM

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.6 ft. - Surface Reinforcement Corroded, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    28.5 ft. - General Photograph

  • General Photograph

    66.1 ft. - General Photograph

  • General Photograph

    147.2 ft. - General Photograph

  • General Photograph

    214 ft. - General Photograph

  • General Photograph

    357.7 ft. - General Photograph

Observations (23)

DistanceCodeObservation
560.2SSS
2SRV
357.7MGP
561MGOGREASE THROUGHOUT THE REACH (5%)
2SAV
66.1MGP
562MSAFLOAT FLIPPED
214MGP
28.5MGP
10.6SRC
560.2SZ30% MAG
2SSS
560.2SAV
147.2MGP
560.2SRC
2SAP
0.1MWM
0MWL
560.2SAP
0AMH8:45 AM
560.2SRV
2SZ30% MAG
561MGOPeeling & Flaking Throughout The Reach

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2019-01-29T09:36:56-08:00
documentation
FRANKLIN, CASTILLO, IGNACIO, SHADLER
is_lateral_inspection
false