Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2019, 08:26 PM
  • 02 1270_02 1269_1222019_123118.mp4

Date
01/22/2019
W/O
PENDING
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00238
PipeID
P04616
Time
12:26 PM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7901
Sewer Name
02 BELVEDERE TRUNK
City
COMMERCE
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Maintenance Related
Project
20190122DF_BELVEDERE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 1270
Downstream MH
02 1269
Dir. of Survey
Downstream
Length Surveyed
460.3 ft.
Total Length
460.3 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 1270 to 02 1269
MH: 02 1270MH: 02 1269downstream0 ft. AMH - Upstream Manhole, Survey Begins - 12:29 PM0.1 ft. MWM - Water Mark, 30 %of cross sectional area0.1 ft. MWL - Water Level, 25 %of cross sectional area272.7 ft. MGP - General Photograph273 ft. MGP - General Photograph283 ft. MGP - General Photograph283.2 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Start288 ft. MGP - General Photograph288 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES293.1 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start295 ft. MGP - General Photograph295 ft. MGP - General Photograph304.4 ft. MGP - General Photograph406.1 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish406.1 ft. B - Broken, at 12 o'clock, within 8 inches of joint: YES, Finish460.3 ft. AMH - Downstream Manhole, Survey Ends - 1:00 PM

Observation photos (11)

  • Water Mark, 30 %of cross sectional area

    0.1 ft. - Water Mark, 30 %of cross sectional area

  • General Photograph

    272.7 ft. - General Photograph

  • General Photograph

    273 ft. - General Photograph

  • General Photograph

    283 ft. - General Photograph

  • Broken, at 12 o'clock, within 8 inches of joint: YES, Start

    283.2 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    288 ft. - General Photograph

  • Broken, at 12 o'clock, within 8 inches of joint: YES

    288 ft. - Broken, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    293.1 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • General Photograph

    295 ft. - General Photograph

  • General Photograph

    295 ft. - General Photograph

  • General Photograph

    304.4 ft. - General Photograph

Observations (16)

DistanceCodeObservation
272.7MGP
406.1FL
288MGP
0.1MWM
283MGP
295MGP
304.4MGP
295MGP
0.1MWL
293.1FL
288B
273MGP
283.2B
460.3AMH1:00 PM
0AMH12:29 PM
406.1B

Properties (4)

custom_field_three
BROKEN/SHIFTED PIPE THROUGHOUT
custom_field_two
1
customer
LACSD
datetime
2019-01-22T12:26:35-08:00