Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2019, 12:36 PM
  • Section#21_15 0752_15 0751__1252019__I0105.mp4

Date
01/25/2019
W/O
0749484
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12952
Time
4:36 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0105
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20190118MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0752
Downstream MH
15 0751
Dir. of Survey
Downstream
Length Surveyed
327.8 ft.
Total Length
327.8 ft.
Structural Index
3
Structural Quick
4L2L
Structural Rating
396
O&M Index
3
O&M Quick
4131
O&M Rating
9
Overall Index
3
Overall Quick
Overall Rating
405
Pipe schematic from manhole 15 0752 to 15 0751
MH: 15 0752MH: 15 0751downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:05AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 55 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG13 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED47.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-50% ROOTS70.6 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG83.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB89.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN155.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - STUB158.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 6" - OPEN173.7 ft. MGO - General Observation - MAG COAT 10% START185.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN233.3 ft. RMJ - Roots Medium Joint, from 11 to 04 o'clock, 40 %, within 8 inches of joint: YESR327.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG327.2 ft. MGO - General Observation - MAG COAT 10% FINISH327.2 ft. MGO - General Observation - ACTIVE MH CONN 3:00327.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED327.8 ft. AMH - Downstream Manhole, Survey Ends - 5:30AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

    13 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

    70.6 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - MAG COAT 10% START

    173.7 ft. - General Observation - MAG COAT 10% START

  • Roots Medium Joint, from 11 to 04 o'clock, 40 %, within 8 inches of joint: YESR

    233.3 ft. - Roots Medium Joint, from 11 to 04 o'clock, 40 %, within 8 inches of joint: YESR

Observations (20)

DistanceCodeObservation
327.2SAMSEVERE AGG
327.2MGOMAG COAT 10% FINISH
155.4TFCSTUB
83.1TFCSTUB
327.2MGOACTIVE MH CONN 3:00
233.3RMJ
327.8AMH5:30AM
2SSSPEELING CONCRETE SEVERE AGG ATTACHED
0AMH5:05AM
185.6TFOPEN
327.2SSSPEELING CONCRETE SEVERE AGG ATTACHED
0MWL
70.6SAMSEVERE AGG
13SSSPEELING CONCRETE SEVERE AGG ATTACHED
173.7MGOMAG COAT 10% START
158.8TFOPEN
2SAMSEVERE AGG
89.5TFOPEN
47.1TFDOPEN-50% ROOTS
0MWM

Properties (4)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2019-01-25T04:36:47-08:00