Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 23, 2019, 08:43 AM
  • Section#13_15 0765_15 0764__1232019__I0099.mp4

Date
01/23/2019
W/O
0749484
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12966
Time
12:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0099
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20190118MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0765
Downstream MH
15 0764
Dir. of Survey
Downstream
Length Surveyed
209.7 ft.
Total Length
209.7 ft.
Structural Index
3
Structural Quick
4423
Structural Rating
22
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
27
Pipe schematic from manhole 15 0765 to 15 0764
MH: 15 0765MH: 15 0764downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM0 ft. MGO - General Observation - ACTIVE MH CONN 3:000 ft. MGO - General Observation - ACTIVE MH CONN 9:002 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING ,PEELING CONCRETE SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. MGO - General Observation - MAG COAT 10% START64.3 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG68 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 6" - OPEN75.9 ft. MGO - General Observation - MAG COAT 30% START88.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - STUB91.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - STUB99.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED118.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN121.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6" - STUB148.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN167.2 ft. MWM - Water Mark, 80 %of cross sectional area183.7 ft. MGO - General Observation - MAG COAT 30% FINISH183.7 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG PEELED AWAY209.4 ft. MGO - General Observation - MH CONN ACTIVE 9:00209.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED209.4 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG209.7 ft. AMH - Downstream Manhole, Survey Ends - 1:20AM

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING ,PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING ,PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • General Observation - MAG COAT 10% START

    2 ft. - General Observation - MAG COAT 10% START

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    64.3 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • General Observation - MAG COAT 30% START

    75.9 ft. - General Observation - MAG COAT 30% START

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    99.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Water Mark, 80 %of cross sectional area

    167.2 ft. - Water Mark, 80 %of cross sectional area

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG PEELED AWAY

    183.7 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG PEELED AWAY

Observations (24)

DistanceCodeObservation
68TBOPEN
167.2MWM
209.4MGOMH CONN ACTIVE 9:00
148.6TFOPEN
91.1TFCSTUB
75.9MGOMAG COAT 30% START
183.7MGOMAG COAT 30% FINISH
64.3SAMSEVERE AGG
209.4SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
2SSSBLISTERING ,PEELING CONCRETE SEVERE AGG ATTACHED
2SAMSEVERE AGG
209.4SAMSEVERE AGG
0MWL
0MWM
99.6SSSPEELING CONCRETE SEVERE AGG ATTACHED
88.9TFCSTUB
0AMH12:50AM
0MGOACTIVE MH CONN 3:00
0MGOACTIVE MH CONN 9:00
118.7TFOPEN
209.7AMH1:20AM
121.2TFCSTUB
2MGOMAG COAT 10% START
183.7SAMSEVERE AGG PEELED AWAY

Properties (4)

custom_field_three
PEELING CONCRETE SEVERE AGG ATTACHED
custom_field_two
2
customer
LACSD
datetime
2019-01-23T00:43:29-08:00