Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2019, 11:01 AM
  • Section#11_15 0815_15 0814__1222019__I0097.mp4

Date
01/22/2019
W/O
0749485
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P13016
Time
3:01 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0097
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190118MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
9.420000076293945 in.
Upstream MH
15 0815
Downstream MH
15 0814
Dir. of Survey
Downstream
Length Surveyed
334.9 ft.
Total Length
334.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0815 to 15 0814
MH: 15 0815MH: 15 0814downstream0 ft. MGO - General Observation - STUB MH CONN 3:000 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - STUB MH CONN 9:000 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:40AM13.8 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN-50% GREASE18 ft. MGO - General Observation - 9.4" NRCP PVCP LINER138.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN173.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN203.2 ft. MGO - General Observation - PVCP LINER257.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN279.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN334.7 ft. MGO - General Observation - STUB MH COINN 9:00334.7 ft. MGO - General Observation - STUB MH CONN 3:00334.9 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (2)

  • General Observation - 9.4" NRCP PVCP LINER

    18 ft. - General Observation - 9.4" NRCP PVCP LINER

  • General Observation - PVCP LINER

    203.2 ft. - General Observation - PVCP LINER

Observations (15)

DistanceCodeObservation
138.7TBOPEN
0MGOSTUB MH CONN 3:00
257.2TBOPEN
334.7MGOSTUB MH COINN 9:00
0MWL
13.8TBDOPEN-50% GREASE
334.7MGOSTUB MH CONN 3:00
334.9AMH5:00AM
18MGO9.4" NRCP PVCP LINER
173.2TBOPEN
203.2MGOPVCP LINER
0MGOSTUB MH CONN 9:00
0MWM
0AMH4:40AM
279.7TBOPEN

Properties (5)

custom_field_three
PVCP LINER GOOD COND
custom_field_two
4
customer
LACSD
datetime
2019-01-22T03:01:42-08:00
lining
PVCP